Metadata-Version: 2.1
Name: sdm-modbus
Version: 0.2.1
Summary: Eastron SDM Modbus parser library
Home-page: https://github.com/nmakel/sdm_modbus
Author: nmakel
Author-email: 
License: MIT License
Platform: UNKNOWN
Classifier: Development Status :: 4 - Beta
Classifier: Programming Language :: Python :: 3.7
Classifier: Operating System :: OS Independent
Classifier: Environment :: Console
Classifier: Natural Language :: English
Classifier: Intended Audience :: Developers
Classifier: License :: OSI Approved :: MIT License
Description-Content-Type: text/markdown
Requires-Dist: pymodbus (>=2.3.0)

# sdm_modbus

sdm_modbus is a python library that collects data from Eastron SDM single- and three-phase kWh meters over Modbus or ModbusTCP.

This repository is a work in progress.

Supported devices:
* SDM120
* SDM630

## Installation

To install, either clone this project and install using `setuptools`:

```python3 setup.py install```

or install the package from PyPi:

```pip3 install sdm_modbus```

## Usage

The script `example.py` provides a minimal example of connecting to and displaying all input and holding registers on a **SDM120** over **ModbusTCP**.

```
usage: example.py [-h] [--unit UNIT] host port

positional arguments:
  host         ModbusTCP address
  port         ModbusTCP port

optional arguments:
  -h, --help   show this help message and exit
  --unit UNIT  Modbus unit
```

Output:

```
{
    'voltage': 236.89999389648438,
    'current': 8.619999885559082,
    'power_active': -1923.699951171875,
    'power_apparent': 2033.04833984375,
    'power_reactive': -657.5999755859375,
    'pfactor': -0.9462323784828186,
    'phase_angle': 0.0,
    'frequency': 49.95000076293945,
    'import_energy_active': 1551.3740234375,
    'export_energy_active': 1335.6939697265625,
    'import_energy_reactive': 0.014999999664723873,
    'export_energy_reactive': 4362.13916015625,
    'total_energy_active': 2887.068115234375,
    'total_energy_reactive': 0.0,
    'demand_time': 1,
    'demand_period': 60,
    'meter_id': 1,
    'relay_pulse_width': 60,
    'network_parity_stop': 0,
    'baud': 2,
    'p1_output_mode': 4,
    'display_scroll_timing': 0,
    'p1_divisor': 0,
    'measurement_mode': 0,
    'indicator_mode': 0
}

SDM120(10.0.0.123:502, unit=0x1):

Input Registers:
    Voltage: 237.00V
    Current: 8.63A
    Power (Active): -1919.70W
    Power (Apparent): 2035.57VA
    Power (Reactive): -676.70VA
    Power Factor: -0.94
    Phase Angle: 0.00°
    Frequency: 50.00Hz
    Imported Energy (Active): 1551.37kWh
    Imported Energy (Active): 1335.69kWh
    Imported Energy (Reactive): 0.01kVAh
    Exported Energy (Reactive): 4362.14kVAh
    Total Energy (Active): 2887.07kWh
    Total Energy (Reactive): 0.00kVAh

Holding Registers:
    Demand Time: 1s
    Demand Period: 60s
    Meter ID: 1
    Relay Pulse Width: 60ms
    Network Parity Stop: N-1
    Baud Rate: 9600
    P1 Output Mode: Export Energy (Active)
    Display Scroll Timing: 0s
    P1 Divisor: 0.001kWh/imp
    Measurement Mode: 0
    Pulse/LED Indicator Mode: Import + Export Energy (Active)
```

## Examples

If you wish to use ModbusTCP the following parameters are relevant:

`host = IP or DNS name of your ModbusTCP gateway, required`  
`port = listening port of the ModbusTCP gateway, required`  
`unit = Modbus device id, default=1, optional`

While if you are using a serial Modbus connection you can specify:

`device = path to serial device, e.g. /dev/ttyUSB0, required`  
`baud = baud rate of your SDM unit, defaults to product default, optional`  
`unit = Modbus unit id, defaults to 1, optional`

Connecting to the meter:

```
    >>> import sdm_modbus

    # SDM120 over ModbusTCP
    >>> device = sdm_modbus.SDM120(host="10.0.0.123", port=502)

    # DM630 over Modbus RTU
    >>> device = sdm_modbus.SDM630(device="/dev/ttyUSB0", baud=9600)
```

Test the connection:

```
    >>> device.connected()
    True
```

Printing the class yields basic device parameters:

```
    >>> device
    SDM120(10.0.0.123:502, unit=0x1)
```

Reading a single input register by name:

```
    >>> device.read("voltage")
    236.89999389648438
```

Read all input registers by passing the `sdm_modbus.registerType.INPUT` enum to `read_all()`. Leave this blank to read both `INPUT` and `HOLDING` registers:

```
    >>> device.read_all(sdm_modbus.registerType.INPUT)
    {
        'voltage': 236.89999389648438,
        'current': 8.619999885559082,
        'power_active': -1923.699951171875,
        'power_apparent': 2033.04833984375,
        'power_reactive': -657.5999755859375,
        'pfactor': -0.9462323784828186,
        'phase_angle': 0.0,
        'frequency': 49.95000076293945,
        'import_energy_active': 1551.3740234375,
        'export_energy_active': 1335.6939697265625,
        'import_energy_reactive': 0.014999999664723873,
        'export_energy_reactive': 4362.13916015625,
        'total_energy_active': 2887.068115234375,
        'total_energy_reactive': 0.0,
    }

    >>> device.read_all(sdm_modbus.registerType.HOLDING)
    {
        'demand_time': 1,
        'demand_period': 60,
        'meter_id': 1,
        'relay_pulse_width': 60,
        'network_parity_stop': 0,
        'baud': 2,
        'p1_output_mode': 4,
        'display_scroll_timing': 0,
        'p1_divisor': 0,
        'measurement_mode': 0,
        'indicator_mode': 0
    }
```

To pretty print all input and holding registers *with* formatting and units:

```
    >>> device.pprint()
    SDM120(10.0.0.123:502, unit=0x1):

    Input Registers:
        Voltage: 237.00V
        Current: 8.63A
        Power (Active): -1919.70W
        Power (Apparent): 2035.57VA
        Power (Reactive): -676.70VA
        Power Factor: -0.94
        Phase Angle: 0.00°
        Frequency: 50.00Hz
        Imported Energy (Active): 1551.37kWh
        Imported Energy (Active): 1335.69kWh
        Imported Energy (Reactive): 0.01kVAh
        Exported Energy (Reactive): 4362.14kVAh
        Total Energy (Active): 2887.07kWh
        Total Energy (Reactive): 0.00kVAh

    Holding Registers:
        Demand Time: 1s
        Demand Period: 60s
        Meter ID: 1
        Relay Pulse Width: 60ms
        Network Parity Stop: N-1
        Baud Rate: 9600
        P1 Output Mode: Export Energy (Active)
        Display Scroll Timing: 0s
        P1 Divisor: 0.001kWh/imp
        Measurement Mode: 0
        Pulse/LED Indicator Mode: Import + Export Energy (Active)
```

If you need more information about a particular register, to look up the units or enumerations, for example:

```
    >>> device.registers["voltage"]
        # address, length, type, datatype, valuetype, name, unit
        (0, 2, <registerType.INPUT: 1>, <registerDataType.FLOAT32: 11>, <class 'float'>, 'Voltage', 'V'))

    >>> device.registers["p1_divisor"]
        (
            63760, 2, <registerType.HOLDING: 2>, <registerDataType.FLOAT32: 11>, <class 'int'>, 
            'P1 Divisor', ['0.001kWh/imp', '0.01kWh/imp', '0.1kWh/imp', '1kWh/imp']
        )
```

Writing to holding registers is also possible. Setting a new baud rate, for example:

```
    >>> device.write("baud", 2)
    WriteMultipleRegisterResponse (28,2)
```

**Remember:** you will need to enable setup mode on your device by pressing the setup button for 5 seconds. You will receive a `Exception Response(134, 6, GatewayNoResponse)` or similar, otherwise.

## Contributing

Contributions are more than welcome, especially testing on existing and other Eastron SDM units.