Table of Contents

Program Version:EnergyPlus-Windows-OMP-32 7.2.0.006, YMD=2013.01.28 16:38

Tabular Output Report in Format: HTML

Building: Building

Environment: San Francisco Intl Ap CA USA TMY3 WMO#=724940

Simulation Timestamp: 2013-01-28 16:38:08


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2013-01-28 16:38:08

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kWh] Energy Per Total Building Area [kWh/m2] Energy Per Conditioned Building Area [kWh/m2]
Total Site Energy 47694.47 51.44 51.44
Net Site Energy 47694.47 51.44 51.44
Total Source Energy 140159.10 151.16 151.16
Net Source Energy 140159.10 151.16 151.16


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050


Building Area

Area [m2]
Total Building Area 927.20
Net Conditioned Building Area 927.20
Unconditioned Building Area 0.00


End Uses

Electricity [kWh] Natural Gas [kWh] Other Fuel [kWh] District Cooling [kWh] District Heating [kWh] Water [m3]
Heating 0.00 5227.69 0.00 0.00 0.00 0.00
Cooling 2222.38 0.00 0.00 0.00 0.00 0.00
Interior Lighting 22566.38 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 13249.20 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2929.16 0.00 0.00 0.00 0.00 0.00
Pumps 888.54 0.00 0.00 0.00 0.00 0.00
Heat Rejection 611.12 0.00 0.00 0.00 0.00 34.60
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 42466.78 5227.69 0.00 0.00 0.00 34.60
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kWh] Natural Gas [kWh] Other Fuel [kWh] District Cooling [kWh] District Heating [kWh] Water [m3]
Heating Boiler 0.00 5227.69 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 2222.38 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 22566.38 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 13249.20 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2929.16 0.00 0.00 0.00 0.00 0.00
Pumps General 888.54 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 611.12 0.00 0.00 0.00 0.00 34.60
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kWh/m2] Natural Gas Intensity [kWh/m2] Other Fuel Intensity [kWh/m2] District Cooling Intensity [kWh/m2] District Heating Intensity [kWh/m2] Water Intensity [m3/m2]
Lighting 24.34 0.00 0.00 0.00 0.00 0.00
HVAC 7.17 5.64 0.00 0.00 0.00 0.04
Other 14.29 0.00 0.00 0.00 0.00 0.00
Total 45.80 5.64 0.00 0.00 0.00 0.04


Utility Use Per Total Floor Area

Electricity Intensity [kWh/m2] Natural Gas Intensity [kWh/m2] Other Fuel Intensity [kWh/m2] District Cooling Intensity [kWh/m2] District Heating Intensity [kWh/m2] Water Intensity [m3/m2]
Lighting 24.34 0.00 0.00 0.00 0.00 0.00
HVAC 7.17 5.64 0.00 0.00 0.00 0.04
Other 14.29 0.00 0.00 0.00 0.00 0.00
Total 45.80 5.64 0.00 0.00 0.00 0.04


Electric Loads Satisfied

Electricity [kWh] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 42466.78 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 42466.78 100.00
     
Total On-Site and Utility Electric Sources 42466.78 100.00
Total Electricity End Uses 42466.78 100.00


On-Site Thermal Sources

Heat [kWh] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 34.60 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 34.60 100.00
Total Water End Uses 34.60 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Time Heating Setpoint Not Met 0.20
Tolerance for Time Cooling Setpoint Not Met 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 1462.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 757.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary